- 3050 -
1
Setpoint channel
Skip frequency bands
© Siemens AG
2 3 4 5 6 7 8
V6.02.00
<2>
-1 -1 -1 -1
y
x
-1
Max
w = p1101[D]
w
w
w
w
w
w
w
w
1
0
c1098 [C]
(100.00)
Skip speed scaling [%]
c1106 [C]
(0.00)
Minimum speed [rpm]
r1114
Setpoint after the direction limiting [rpm]
r1170
Speed controller setpoint sum [rpm]
[3080.8]
[3040.8]
Minimum speed
0.000 ... 19500.000 [rpm]
p1080 [D] (0.000)
r1112
Speed setpoint after minimum
limiting [rpm]
Skip speed 3
0.000 ... 210000.000 [rpm]
p1093 [D] (0.000)
Skip speed 4
0.000 ... 210000.000 [rpm]
p1094 [D] (0.000)
Skip speed 2
0.000 ... 210000.000 [rpm]
p1092 [D] (0.000)
Skip speed 1
0.000 ... 210000.000 [rpm]
p1091 [D] (0.000)
<1> <1> <1> <1>
r1099.0
1 = r1170 within the skip band
Effective minimum
speed
A skip speed of "0" deactivates the skip band.
If the drive is not stopped via the input setpoint, but via controlled intervention, the lower hysteresis branch is relevant after a subsequent run-up.
<1>
Skip speed
bandwidth
<2>
[3051.1]
Figure14-65 3050 - Skip frequency bands
Functions
14.9Setpoint channel
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 453