- 6310 -
1
Vector control
U/f control, Resonance damping
© Siemens AG
2 3 4 5 6 7 8
V6.02.00
<1>
6 %
10 % 95 %
1
f/f
Mot N
+
r0066
Output frequency [Hz]
U/f mode resonance damping gain
0.00 ... 100.00
p1338 [D] (0.00)
U/f mode resonance damping maximum frequency
0.00 ... 3000.00 [Hz]
p1349 [D] (0.00)
[6300.7]
Resonance damping
[6730.5]
[6731.5]
<1>
For p1349 = 0: the limit is 0,95 · f Mot N 45 Hz.
U/f mode resonance damping filter time constant
1.00 ... 1000.00 [ms]
p1339 [D] (20.00)
r0078[0]
Current actual value torque-
generating Unsmoothed [Arms]
[6715.8]
Figure14-115 6310 - Resonance damping
Functions
14.10Closed-loop drive control
SINAMICS G220 converter
506 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB