Description of function
The following settings are available to select:
Table 14-72 Setting of technological application for closed-loop speed control
0 Standard drive
Factory setting for closed-loop speed control with or without
speed encoder
In all applications that do not 󹪝t the other setting options.
1 Pumps and fans
Optimized utilization of the converter output voltage by re‐
ducing the voltage reserve at higher speeds
If high load surges in the range of low and medium speeds
cannot be ruled out, we recommend setting p501=0.
Applications involving pumps and fans
2 Encoderless control down to f =
0 (passive loads)
Setting for encoderless closed-loop control of induction mo‐
tors and reluctance motors
Speed-controlled operation of induction motors at low
speeds
Speed-controlled operation of reluctance motors at low
speeds using the pulse technique (license required)
A passive load cannot accelerate the current-free motor.
Examples are pumps, fans, extruders, but not hoisting gear
3 Pumps and fans, e󹪟ciency opti‐
mization
Setting for control of induction motors
Suitable for applications without dynamic requirements for
speed and load changes
Applications involving pumps and fans
E󹪟ciency optimization
Less energy consumption and reduced noise
The setting only makes sense for steady-state operation with
slow speed changes. We recommend the setting 0 if load
surges in operation cannot be ruled out.
5 Starting with high break loose
torque
Setting for encoderless control (all motor types)
For speed-controlled operation at low speeds, the current is
raised via p1610.
A break loose torque is a high load in the lower speed range
Increased default setting of the static torque setpoint (p1610)
6 High load inertia
Setting for drives with high power and a total moment of
inertia at least 5 times greater than the motor moment of
inertia
Increased preset for speed actual value smoothing
Optimized speed controller preset
Functions
14.10Closed-loop drive control
SINAMICS G220 converter
510 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB