DC braking is available in 4 variants:
Internal DC braking
0''
%$CSBLJOHBDUJWF
%$CSBLJOHTFMFDUFE
O
Q
U
If the binary signal sink c1230 has a 1 signal, then the converter switches o󹪜 the motor current
for the duration of the motor de-excitation time p0347. The drive behaves in the same way as
it does in response to an OFF2 command.
After the motor de-excitation time, the converter brakes the motor using DC braking.
When binary signal sink c1230has a0 signal, the converter exits DC braking.
DC braking for OFF1/OFF3
4UBSUJOHTQFFE
5JNF
0''PS0''
0''
%$CSBLJOHBDUJWF
0''PS0''
O
Q
U
After an OFF1 or OFF3 command, the converter brakes the motor along the OFF1 or OFF3 down
ramp to the speed to start DC braking.
As soon as the motor speed falls below the speed to start DC braking, the converter switches o󹪜
the motor current for the duration of the motor de-excitation time p0347. The drive behaves in
the same way as it does in response to an OFF2 command.
After the motor de-excitation time, the converter brakes the motor using DC braking.
The converter exits DC braking after the DC braking time.
Functions
14.11Drive functions
SINAMICS G220 converter
592 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB