Description of function
The motor converts braking energy of the load into heat.
_
_
&Ȍ

+O
O
O
U
Figure14-188 Energy 󹪞ow during compound braking
Features of DC braking:
No constant braking torque
No braking torque at standstill
The converter activates the compound braking dependent on the DC link voltage. Above a DC
link voltage threshold value (r1282), the converter adds a DC current to the motor current.
The DC current brakes the motor and prevents the DC link voltage from increasing above a
critical value.
8JUIDPNQPVOECSBLJOH
"EEJUJWF%$
8JUIPVUDPNQPVOECSBLJOH
4QFFE
.PUPSDVSSFOU
%$MJOLWPMUBHF
S
U
U
U
U
U
U
Figure14-189 Braking of the motor with and without active compound braking
Functions
14.11Drive functions
SINAMICS G220 converter
602 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB