The minimum clearance is applicable for the head and the entire torso of the human body.
Shorter distances are possible for extremities.
Table 4-1 Evaluation of the electromagnetic elds
Frequency range
0Hz...100kHz 100kHz...300GHz
Electric eld strength Limit values not exceeded Limit values not exceeded
Magnetic ux density Evaluation in the following table Limit values not exceeded
Table 4-2 Minimum clearance based on magnetic ux density (0Hz...100kHz)
General Individuals with active implants
Converter with
degree of protec‐
tion IP20 in a
closed control
cabinet
Converter with degree
of protection IP20 in an
open control cabinet
or converter in degree
of protection IP55
Converter with degree of
protection IP20 in a closed
control cabinet
Converter with degree
of protection IP20 in an
open control cabinet
or converter in degree
of protection IP55
0cm (0 inch) 25cm (10inch) The limit value of 100µT
(RMS) at 50Hz is not excee‐
ded. Must be assessed de‐
pending on the active im‐
plant.
Must be assessed de‐
pending on the active
implant.
Application planning
4.1Protection of persons from electromagnetic elds
SINAMICS G220 converter
62 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB