Dry running protection/broken belt
- 8014 -
1
Signals and monitoring functions
Load monitoring (part 2)
© Siemens AG
2 3 4 5 6 7 8
V6.02.00
<1>
Load monitoring speed threshold value 1
0.00 ... 210000.00 [rpm]
p2182 [D] (150.00)
Load monitoring speed threshold value 2
0.00 ... 210000.00 [rpm]
p2183 [D] (900.00)
Load monitoring speed threshold value 3
0.00 ... 210000.00 [rpm]
p2184 [D] (1500.00)
Load monitoring torque
threshold 1 lower
0.00 ... 20000000.00 [Nm]
p2186 [D] (0.00)
Load monitoring torque
threshold 1 upper
0.00 ... 20000000.00 [Nm]
p2185 [D] (10000000.00)
Load monitoring torque
threshold 2 lower
0.00 ... 20000000.00 [Nm]
p2188 [D] (0.00)
Load monitoring torque
threshold 2 upper
0.00 ... 20000000.00 [Nm]
p2187 [D] (10000000.00)
Load monitoring torque
threshold 3 upper
0.00 ... 20000000.00 [Nm]
p2189 [D] (10000000.00)
Load monitoring torque
threshold 3 lower
0.00 ... 20000000.00 [Nm]
p2190 [D] (0.00)
M [Nm]
n [rpm]
Tolerance
bandwidth
Monitoring torque and load drop (p2193 =1)
<1>
M [Nm]
n [rpm]
Load monitoring stall
monitoring torque threshold
0.00 ... 20000000.00 [Nm]
p2168 [D] (10000000.00)
Load monitoring torque
threshold 3 lower
0.00 ... 20000000.00 [Nm]
p2190 [D] (0.00)
Load monitoring torque
threshold 1 lower
0.00 ... 20000000.00 [Nm]
p2186 [D] (0.00)
Load monitoring torque
threshold 2 lower
0.00 ... 20000000.00 [Nm]
p2188 [D] (0.00)
Load monitoring torque
threshold no load
0.00 ... 20000000.00 [Nm]
p2191 [D] (0.00)
Load monitoring speed threshold value 1
0.00 ... 210000.00 [rpm]
p2182 [D] (150.00)
Load monitoring speed threshold value 2
0.00 ... 210000.00 [rpm]
p2183 [D] (900.00)
Load monitoring speed threshold value 3
0.00 ... 210000.00 [rpm]
p2184 [D] (1500.00)
Load monitoring stall monitoring upper threshold
0.00 ... 210000.00 [rpm]
p2165 [D] (0.00)
Pump/fan monitoring (p2193 = 4/5)
Pump/fan characteristics
Leakage
Only for pump applications.
Figure14-213 8014 - Load monitoring (Part 2)
Functions
14.11Drive functions
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 643