Transition to STO
SBR ends as soon as the actual speed value is below the STO
switch-o󹪜 speed (p9560).
The converter activates STO.
The converter activates STO even if SS1 is deselected in the
meantime.
The converter signals the status "STO active" (r9722.0).
STO interrupts the torque-generating supply of energy to the
motor and prevents the motor from unexpectedly restarting.
The motor coasts down to a standstill.
Deselection of SS1
The converter detects deselection of SS1.
The converter deactivates STO.
Signal change at ON/OFF1
from 1 to 0
The converter is ready to start again.
Signal change at ON/OFF1
from 0 to 1
The motor starts again.
Parameters
The following list contains the parameters of the "Safe Stop 1 with braking ramp monitoring
(SS1-r)" function.
Number Name Unit
p1135[0...n] OFF3 ramp-down time [s]
p9560 SI STO shutdown velocity [mm/min]
p9560 SI STO shutdown velocity [rpm]
p9581 SI SBR reference velocity [mm/min]
p9581 SI SBR reference velocity [rpm]
p9582 SI SAM/SBR delay time [ms]
p9583 SI SBR reference time [s]
p9603.0...1 SI control
p9604.0...30 SI enable
p9606 SI SS1 function speci󹪝cation
r9714[0...4] SI diagnostics velocity [mm/min]
r9714[0...4] SI diagnostics velocity [rpm]
r9720.0...15 SI control word
r9722.0...15 SI status signals
c10023 SI SS1 input terminal
r10353.0...17 SI SS1 select cause
Functions
14.12Safety Integrated
SINAMICS G220 converter
668 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB