Description of function
/FHBUJWF
4QFFEMJNJU
4QFFE
CFMPXMJNJUWBMVF
)ZTUFSFTJT
)ZTUFSFTJT
4QFFEMJNJU
.PUPS
"DUJPO
44.EFTFMFDUJPO
$POWFSUFS
SFTQPOTF
44.
U
U
44.
W
U
Figure14-233 Representation of SSM
Action Motor/converter response
Selection of SSM
The converter detects when SSM is selected.
If the speed of the motor is between the speed limit and the
negative speed limit, the converter sets the signal "Speed below
limit value" (p9722.15=1).
Exceeding the velocity limit
If the speed of the motor exceeds the speed limit, the converter
resets the signal "Speed below limit value" (p9722.15=0).
Falling below the velocity lim‐
it
If the speed of the motor falls below the speed limit minues the
hysteresis, the converter sets the signal "Speed below limit val‐
ue" (p9722.15=1).
Falling below the negative ve‐
locity limit
If the speed of the motor falls below the negative speed limit,
the converter resets the signal "Speed below limit value"
(p9722.15=0).
Exceeding the negative veloc‐
ity limit
If the speed of the motor exceeds the negative speed limit plus
the hysteresis, the converter sets the signal "Speed below limit
value" (p9722.15=1).
Functions
14.12Safety Integrated
SINAMICS G220 converter
674 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB

Table of Contents