Description of function
The PROFIsafe conguration encompasses the following settings:
Table 14-94 PROFIsafe settings
Settings Explanation
PROFIsafe telegram number
(p9611)
Selection of the PROFIsafe telegram
PROFIsafe telegrams can be used for various purposes:
• Telegram 30:
Control of the functions
• Telegram 902:
Control of the functions + transfer of the F-DI status via PROFIsafe (c10050) + trans‐
fer of the SLS limit value via PROFIsafe (p9604.9)
Supplementary telegram 700 is available if you wish to provide non-safety-related di‐
agnostics of the safety functions on the higher-level control system.
F-source address (p9613)
F-destination address (9610)
F-monitoring time (p9614)
When using PROFIsafe address type 1, the uniqueness of the PROFIsafe address is only
ensured by the F-destination address.
When using PROFIsafe address type 2, the uniqueness of the PROFIsafe address is en‐
sured by the combination of F-source address and F-destination address.
The PROFIsafe address must be unique throughout the network and the CPU. The PRO‐
FIsafe address is unique if these conditions are satised:
• The F-source address of the F-CPU is unique throughout the network.
• The F destination address of the converter is unique throughout the CPU.
A valid, current PROFIsafe telegram must have been received from the F-CPU within the
monitoring time. This ensures the following:
• Detecting failures and faults
• Responses are initiated that keep the F-system in a safe state or transition it into a
safe state
Response to PROFIsafe failure
(p9612)
Selection option for the stop response of the converter in the event of a PROFIsafe
communication failure or error
Parameters
The following list contains the parameters of the "PROFIsafe conguration" function.
Number Name Unit
p9610 SI PROFIsafe destination address
p9611 SI PROFIsafe telegram selection
p9612 SI stop response for failure or control fault
p9613 SI PROFIsafe source address
p9614 SI PROFIsafe F_watchdog time [ms]
p10000.0...2 SI F-DI enable
p10002 SI F-DI changeover discrepancy time [ms]
Functions
14.12Safety Integrated
SINAMICS G220 converter
684 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB