- 7035 -
1
Technology functions
Bypass
© Siemens AG
2 3 4 5 6 7 8
V6.02.00
tp0346
t
t
t
t
t
t
t
p1264
p1263
p1274[1]
p1262 +
p1274[0]
p1274[0]
p1274[0]
p1274[1]p1274[1]
K2
K1
.
.
.
+24 V OUT
DO 1
DO 2
DI 3
DI 4
<1>
K2
K1
0
1
1
0
1
0
0
1
0
1
T1 T2
T1 T2
<3>
K1
K2
<2>
<2>
Bypass speed threshold [rpm]
p1265 (1480.00)
r1261
r1261.0..14
Bypass control/status word
p1260 p1274[0..1]
<1>
<2>
<3>
c1266
(0)
Bypass control command
1 = Bypass via signal (r1266)
p1267.0 (0)
1 = Bypass via reaching the speed threshold
p1267.1 (0)
Switch motor/line supply
0 ... 5000 [ms]
p1274[1] (1000)
Switch motor/drive
0 ... 5000 [ms]
p1274[0] (1000)
c1269[1]
(1261.1)
Switch motor/line supply
c1269[0]
(1261.0)
Switch motor/drive
c1266
(0)
Bypass control command
Flying restart must be activated for the bypass function (p1200 = 1 or 4).
Following bypass functions are possible:
Bypass function when activating via a control signal (p1267.0 = 1).
Bypass function depending on the speed (p1267.1 = 1).
Contactors K1 and K2 must be interlocked so that they cannot close at the same time. In order to
prevent line contactor K2 from inadvertently closing, K2 should be closed via digital output DO 2
that is not preassigned.
Monitoring time for K2:
Line operation
Monitoring time for K1:
Inverter operation
Feedback signal from K2:
Line operation
r1261.1
1 = Command switch motor - Line supply Close
Signal for contactor K2:
Line operation
r1261.0
1 = Command switch motor - Power unit Close
Feedback signal from K1:
Inverter operation
Signal for contactor K1:
Inverter operation
Inverter
operation
Switchover
phase
Line
operation
Switchover
phase
Inverter
operation
Example: Activation via a control signal (p1267.0 = 1)
Bypass
configuration
n_set
Power up
Flying
restart
Line
Figure14-264 7035 - Bypass
Functions
14.13Technology functions
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 727