12.Enter the password for your UMAC account.
13.If the connection has been successfully established, the PC displays:
D:\IIOT\IIoT_upgrade> sftp xx0@169.254.1.42
xx0@169.254.1.42's password:
Connected to 169.254.1.42.
sftp> _
14.Enter command "cd p4":
sftp> cd p4
sftp> _
15.Load the le with the rmware update to the user partition of the OM-IIoT using command
"put -f SINAMICS_IIoT_Module_rmware_Vxx_xx_xxx_xxx.zip".
"SINAMICS_IIoT_Module_rmware_Vxx_xx_xxx_xxx.zip" is the le name of the rmware
update:
sftp> put -f SINAMICS_IIoT_Module_firmware_V01_00_013_000.zip
16.When loading the le, LED COM on the OM-IIoT ashes red and orange alternating:
17.Wait until the converter has completely loaded the le for the rmware update:
sftp> put -f SINAMICS_IIoT_Module_firmware_V01_00_013_000.zip
Uploading SINAMICS_IIoT_Module_firmware_V01_00_013_000.zip to /p4/
SINAMICS_IIoT_Module_firmware_V01_00_013_000.zip
SINAMICS_IIoT_Module_firmware_V01_00_013_000.zip
100% 1170MB 10.2MB/s 01:54
sftp> _
After loading, LED COM on the OM-IIoT lights up green:
18.Enter command "bye":
sftp> bye
D:\IIOT\IIoT_upgrade> _
19.Switch o the converter supply voltage.
20.Wait until all LEDs on the converter are dark.
21.Switch on the converter supply voltage again.
22.The LED COM on the OM-IIoT temporarily lights up orange:
23.If the rmware versions in the OM-IIoT and in the loaded le dier, then the OM-IIoT updates
the rmware.
It takes approximately 5 minutes to update the rmware.
When updating the rmware, LED COM on the OM-IIoT ashes red and green alternating:
Corrective maintenance
16.4Firmware update of option module OM-IIoT
SINAMICS G220 converter
772 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB