7. The user-dened settings are deleted.
RDY COM Description
Factory settings are being restored
Factory settings have been restored
Restoring factory settings unsuccessful
8. Remove the memory card.
9. Switch o the converter supply voltage.
Result
All user-dened converter settings are deleted.
The converter rmware is unchanged.
After the manual reset to the factory setting, access to the web server is possible via the
service interface (X127) and via the PROFINET interface (X150). For access via the service
interface (X127), use the secure transmission protocol HTTPS.
If option module OM-IIoT is inserted, then the settings of interface X128 to the edge device
are deleted.
Corrective maintenance
16.6Full reset of all device settings
SINAMICS G220 converter
778 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB