Property Data
Analog output AO0 16-bit resolution
Operating mode selection:
• 0V…10V, minimum load 10kΩ
• 0mA…20mA, maximum load 500Ω
Minimum response time: 0.25ms
<50mV oset at 0%
Temperature sensor Measuring current 2mA
Rated value Rated value incl. maximum
tolerance
PTC Short-circuit monitoring < 20Ω < 35Ω
Overtemperature > 1650Ω > 1620Ω
KTY84 Short-circuit monitoring < 50Ω < 65Ω
Wire break > 1630Ω > 1600Ω
Pt1000 Short-circuit monitoring < 603Ω < 620Ω
Wire break > 1720Ω > 1690Ω
Failsafe
digital input F-DI0
Type 3 according to IEC61131-2
Input voltage ≤30V
Minimum response time 1ms
Failsafe
digital output F-DO
Minimum load resistance 48Ω
Maximum load resistance 130000Ω
Short-circuit protection
Overload protection
Minimum response time 1ms
Technical data
17.10Inputs and outputs
SINAMICS G220 converter