15.3 Electrical Requirements
The site must satisfy the following electrical requirements for the proper Mediant 8000
installation.
Table
15-4: Electrical Requirement
Item Requirement
Power Feeding In order to maintain the full HA capabilities of the system, a centralized DC
power system must be used as specified in UL60950-1, CAN/CSA-C22.2 NO
60950-1-03 Annex NAB.
Outlets DC outlets are required for connecting the Mediant 8000. For more information,
see 'Power System' on page 41.
Circuit breaker To meet the system power HA scheme, the system should not be current limited
to less than 60A. If a circuit breaker is used, it must be 60A or higher rated.
Power
consumption
A fully occupied Mediant 8000 chassis in a TP-6310 (8+1) DC power
configuration has the following average power consumption:
TP-6310 1494 watts at 48 VDC
A fully occupied Mediant 8000 chassis in a TP-8410 (5+1) DC power
configuration has the following average power consumption:
TP-8410 1200 watts at 48 VDC