Maintenance Object Repair Procedures
555-233-123
10-712 Issue 4 May 2002
2018 ABORT Applicable only when testing Duplication Interface A.
1. Refer to STBY-SPE (Standby SPE) Maintenance
documentation.
2033 ABORT Internal system error
1. Retry the command at 1-minute intervals a maximum of 5
times.
2052 ABORT Only occurs when attempting to reset Duplication Interface A. If
SPE B is not in Standby Mode, ready to take over, then this
test aborts.
1. Resolve any STBY-SPE errors and alarms.
2. Use refresh spe command to place SPE B in Standby
Mode.
3. Repeat the test.
2000 FAIL The software timed out waiting for Duplication Interface circuit
pack to respond to the background test query.
1. Rerun the test.
2. If the test fails with Error Code 2000 again, then deal with
the Duplication Interface Circuit Pack Status Query Test
(#315) results first.
FAIL The sanity timer circuit on the Duplication Interface circuit pack
is defective. The Duplication Interface circuit pack should be
replaced.
1. Follow the procedure for replacing Common Control circuit
packs, and replace the Duplication Interface circuit pack.
2. Rerun the test.
NO
BOARD
The Duplication Interface circuit pack has failed to handshake
with either the active Maintenance/Tape Processor (in the case
of Duplication Interface circuit pack A) or the Duplication
Interface circuit pack A (in the case of Duplication Interface
circuit pack B).
1. Refer to NO BOARD description for the Duplication
Interface Circuit Pack Status Query Test (#315).
PASS The Duplication Interface circuit pack successfully reset. The
Duplication Interface circuit pack may still have problems
related to any of the other Duplication Interface circuit pack
tests. Follow up on any other test failures.
Table 10-263. TEST #273 Duplication Interface Circuit Pack
Sanity Circuit Test — Continued
Error
Code
Te s t
Result Description/Recommendation
Continued on next page