FL-DATA (Flash Data Consistency)
Issue 4 May 2002
10-837555-233-123
68 FAIL The update files and load vintages are different in both
SPEs. The Standby SPE has the most current update file.
69 FAIL The update files, load vintages, and translations are
different in both SPEs. The Standby SPE has the most
current update file, and the Active SPE has the most
current translations.
70 FAIL The update files, load vintages, and translations are
different in both SPEs. The Standby SPE has the most
current update file and translations.
1. Follow the procedures for Error Code 4 to get the
correct load vintage. After running test card-mem
long, check for Error Codes 32 or 64. Follow the
recovery procedure under the applicable error code.
72 FAIL The update files and announcements are different in both
SPEs. The Standby SPE has the most current update file
and the Active SPE has the most current announcements.
1. Issue the save announcements command to save
announcements on both SPEs.
2. Follow the procedures for Error Code 64.
73 FAIL The update files, translations, and announcements are
different in both SPEs. The Active SPE has the most
current translations and announcements, and the Standby
SPE has the most current update file.
74 FAIL The update files, translations, and announcements are
different in both SPEs. The Active SPE has the most
current announcements, and the Standby SPE has the
most current update file and translations.
1. Issue save translations.
2. Issue save announcements.
3. Follow the procedures for Error Code 64.
Table 10-303. TEST #421 Flash Data Consistency Check Test — Continued
Error Code
Te s t
Result Description/Recommendation
Continued on next page