STBY-SPE (Standby SPE)
Issue 4 May 2002
10-1555555-233-123
2051 ABORT When attempting to refresh Standby SPE memory from Active SPE
memory, the Active SPE could not determine the status of one of the
Duplication Interface circuit packs, or it determined that one of the
Duplication Interface circuit packs was defective.
1. Check for carrier A Duplication Interface circuit pack errors and
alarms. Refer to DUPINT (Duplication Interface Circuit Pack)
Maintenance documentation and follow the prescribed
procedures.
2. Check for carrier B Duplication Interface circuit pack errors and
alarms. Refer to DUPINT (Duplication Interface Circuit Pack)
Maintenance and follow the prescribed procedures.
3. Check the Inter-Carrier Cable to see if the cable is loose or
disconnected. If so, follow the repair procedures for
reconnecting the Inter-Carrier Cable described in Chapter 6,
‘‘Reliability Systems: A Maintenance Aid’’.
4. If all problems found in Steps 1, 2, and 3 have now been
repaired, proceed with Step 8. If no problems were found in
Steps 1, 2, and 3, proceed with Step 5.
5. Issue display errors and check to see if Error Type 80 is
logged against STBY-SPE. If so, the problem is the carrier A
Duplication Interface circuit pack. Replace the carrier A
Duplication Interface circuit pack as described in Chapter 6,
‘‘Reliability Systems: A Maintenance Aid’’ and proceed with
Steps 8, 9, and 10.
6. Issue display errors and check to see if Error Type 82 is
logged against STBY-SPE. If so, the problem is the carrier B
Duplication Interface circuit pack. Replace the carrier B
Duplication Interface circuit pack as described in Chapter 6,
‘‘Reliability Systems: A Maintenance Aid’’ and proceed with
Steps 8, 9, and 10.
7. If Error Type 80 or 82 is not logged, escalate the problem.
Table 10-578. Test Result Error Codes Associated with the Standby SPE — Continued
Error
Code
Tes t
Result Description/Recommendation
Continued on next page