304 Upgrade and Maintenance Manual RX2540 M4
Expansion cards and backup units
9.10.4.5 Removing a GPGPU card
Ê Remove the GPGPU card, see section "Removing a GPGPU card (FL)" on
page 298.
9.10.4.6 Installing the slot cover riser module 2
Ê Install the slot cover, see section "Installing the slot cover for the riser
module 2" on page 272.
9.10.4.7 Installing the rear air grid riser module 2
Ê Install the rear air grid, see section "Installing the rear air grid riser module
2" on page 279.
9.10.4.8 Installing the air duct
I If no GPGPU card is installed in riser module 2 you have to order a new
air duct to direct the airflow directly onto the CPU heat sinks and memory
slots.
Ê Install the air duct, see section "Installing the air duct" on page 89.
9.10.4.9 Concluding steps
Ê "Reassembling" on page 63
Ê "Connecting the power cord" on page 67
Ê "Switching on the server" on page 70
Ê "Resuming BitLocker functionality" on page 112