• Oset can be set
Parameter p0783 determines the oset for the analog output.
• Scaling can be set
The converter uses a scaling characteristic to convert the value range -100% ... 100% of the
internal signal to the voltage range 0 V ... 10 V or current range 4 mA ... 20 mA, whichever
is suitable. The two points (x1, y1) and (x2, y2) dene the scaling characteristic.
$VSSFOUPVUQVUN"N"7PMUBHFPVUQVU77
QQ
Y
Q
Z
Q
Y
Q
Z
Q
Y
Q
Z
Q
Y
Q
Z
Q
7N"
Figure14-39 Scaling of the analog output
Parameters
The following list contains the parameters of the "Analog outputs" function.
Number Name Unit
c0771[0] Analog output signal
r0772[0] Analog output actual output value referred [%]
p0773[0] Analog output smoothing time constant [ms]
r0774[0] Analog output actual output voltage/current
p0775[0] Analog output, activate absolute value generation
p0776[0] Analog output type
p0777[0] Analog output characteristic value x1 [%]
p0778[0] Analog output characteristic value y1
p0779[0] Analog output characteristic value x2 [%]
p0780[0] Analog output characteristic value y2
c0782[0] Analog output inversion
p0783[0] Analog output oset
Functions
14.8Inputs/outputs
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 429