Digital inputs simulation
mode setpoint
p0796
Digital inputs simulation mode
p0795
r0722
r0722.0..22
Digital inputs status
r0723
r0723.0..22
Digital inputs status inverted
- 2221 -
1
Input/output terminals
Digital inputs, electrically isolated (DI 0 … DI 5, DI 21 ... DI 22)
© Siemens AG
2 3 4 5 6 7 8
V6.02.00
1
0
1
0
1
0
1
0
1
1
1
1
0
1
1
0
1
T 0
T 0
T 0
T 0
T 0
T 0
&
&
&
&
&
&
1 = DI 0 (X131.1) Simulation
p0795.0 (0)
r0723
r0723.0
1 = DI 0 (X131.1)
1
r0722
r0722.1
1 = DI 1 (X131.2)
r0722
r0722.2
1 = DI 2 (X131.5)
r0722
r0722.3
1 = DI 3 (X131.6)
r0722
r0722.4
1 = DI 4 (X131.8)
r0722
r0722.5
1 = DI 5 (X131.9)
p0795.2
p0724
p0724
p0724
p0724
p0724
p0796.1
p0796.2
p0796.3
p0796.4
p0796.5
1 = DI 0 (X131.1)
p0796.0 (0)
24 V
3,3 V
DI 5
DI 2
DI 1+
DI 0
DI 3+
DI 4
DI 3–
DI 1–
r0723
r0723.1
1 = DI 1 (X131.2)
r0723
r0723.2
1 = DI 2 (X131.5)
r0723
r0723.3
1 = DI 3 (X131.6)
r0723
r0723.4
1 = DI 4 (X131.8)
r0723
r0723.5
1 = DI 5 (X131.9)
Sampling time of the digital inputs: p0799[0] (2 ms)
p0795.1
p0795.3
p0795.4
p0795.5
1
0
1
0
1
T 0
T 0
&
&
r0723
r0723.21
1 = DI 21 (X130.2/3)
r0722
r0722.21
1 = DI 21 (X130.2/3)
1
r0722
r0722.22
1 = DI 22 (X130.6/7)
p0724
p0796.22
24 V
3,3 V
DI 22+
DI 21+
DI 22–
r0723
r0723.22
1 = DI 22 (X130.6/7)
DI 21–
p0724
p0796.21
p0795.21
p0795.22
r0722
r0722.0
1 = DI 0 (X131.1)
Digital inputs debounce time
0.000 ... 20.000 [ms]
p0724 (4.000)
Figure14-43 2221 – Digital inputs isolated (DI 0 … DI 5, DI 21 ... DI 22)
Functions
14.8Inputs/outputs
SINAMICS G220 converter
432 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB