- 2256 -
1
Input/output terminals
Analog inputs as Digital inputs (DI 11 … DI 12)
© Siemens AG
2 3 4 5 6 7 8
V6.02.00
Sampling time of the digital inputs: p0799[1] (4 ms)
Digital inputs simulation
mode setpoint
p0796
Digital inputs simulation mode
p0795
r0722
r0722.0..22
Digital inputs status
r0723
r0723.0..22
Digital inputs status inverted
1
0
1
0
1
T 0
T 0
&
&
1 = DI 11 (X132.1/2) AI0 Simulation
p0795.11 (0)
1
p0724
1 = DI 11 (X132.1/2) AI0
p0796.11 (0)
Digital inputs debounce time
0.000 ... 20.000 [ms]
p0724 (4.000)
r0722
r0722.12
1 = DI 12 (X132.5/6) AI1
r0723
r0723.12
1 = DI 12 (X132.5/6) AI1
r0722
r0722.11
1 = DI 11 (X132.1/2) AI0
r0723
r0723.11
1 = DI 11 (X132.1/2) AI0
1 = DI 12 (X132.5/6) AI1 Simulation
p0795.12 (0)
1 = DI 12 (X132.5/6) AI1
p0796.12 (0)
1.6 V 4.0 V
0
1
1.6 V 4.0 V
0
1
AI 1+
(DI 12)
AI 0+
(DI 11)
Figure14-44 2256 - Analog inputs as digital inputs (DI 11 … DI 12)
Functions
14.8Inputs/outputs
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 433