- 3070 -
1
Setpoint channel
Extended ramp-function generator
© Siemens AG
2 3 4 5 6 7 8
V6.02.00
<4>
T
up
T
dn
0 1
0
1
1
0
0
1
1
[2634.7]
r1198
r1198.15
1 = Bypass ramp-function generator
r0898
r0898.6
1 = Enable speed setpoint
r0898
r0898.5
1 = Continue ramp-function generator
r1119
Ramp-function generator
setpoint at the input [rpm]
c1138 [C]
(100.00)
Ramp-function generator
ramp-up time scaling [%]
c1141
<3>
0
0
Ramp
flattening-off
1 = Internal RFG enable
0 = Internal quick stop
[2634.7]
[2634.7]
[3051.8]
[3080.8]
c1142
[2501.7]
[2501.7]
0 = Internal quick stop
OFF3 ramp-down time
0.000 ... 5400.000 [s]
p1135 [D] (1.000)
[3051.8]
Ramp-function gen. tolerance for ramp-up and ramp-down active
0.000 ... 1000.000 [rpm]
p1148 [D] (19.800)
Reference value for the
ramp-function generator
r0898
r0898.4
1 = Enable ramp-function generator
c1140
[2501.7]
0
1
0
[3080.1]
Freeze ramp-function generator
n_set_5
Other status bits
Ramp-up active
Ramp-down active
Ramp-function
generator,
status bits
r1149
Ramp-function generator
acceleration [rev/s²]
With jog 1 or jog 2 (c1055 OR c1056 =1):
Freeze of ramp-function generator is locked (r0898.5 = 1-signal).
With simultaneous jog 1 and 2 (c1055 = c1056 = 1):
ramp-function generator is frozen and the last setpoint remains effective (r0898.5 = 0-signal).
With activated Technology controller (c2200 > 0, p2251 =
0) the ramp-function generator is bypassed (r2349.5).
<2>
<1>
<1>
[3080.5]
&
y
x
c1139 [C]
(100.00)
Ramp-function generator
ramp-down time scaling [%]
Ramp-function generator ramp-up time [s]
p1120 [D] (10.000)
Ramp-function generator ramp-down time [s]
p1121 [D] (10.000)
y
-p1082
Ti Tf
x
y
t
y
dy/dt
p1082
TfTiTfTiTfTiTfTi
Extended ramp-
function generator
0 1 0 1
Ramp-function generator initial rounding-off time [s]
p1130 [D] (0.000)
OFF3 initial rounding-off time [s]
p1136 [D] (0.010)
Ramp-function generator final rounding-off time [s]
p1131 [D] (0.000)
OFF3 final rounding-off time [s]
p1137 [D] (0.000)
T
up
T
dn
T
up
eff
T
dn
eff
<2> <2>
Effective ramp-up time: Tup_eff = Tup + (Ti/2 + Tf/2)
Effective ramp-down time: Tdn_eff = Tdn + (Ti/2 + Tf/2)
p1082
<4>
c1143 [C]
(0)
Ramp-function generator, accept setting value
c1144 [C]
(0.00)
Ramp-function generator setting value [rpm]
After a 0/1 signal: The ramp-function generator restarts. The ramp-function generator output starts at 0.
<3>
0
1
x
y
–
+
[2505.7]
0 0
0 1 0 1
Figure14-74 3070 - Extended ramp-function generator
Functions
14.9Setpoint channel
SINAMICS G220 converter
460 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB