- 6491 -
1
Vector control
Flux control configuration
© Siemens AG
2 3 4 5 6 7 8
V6.02.00
[6722.5], [6837.5]
01
...
00
p1401.0 [D]
1 = Flux setpoint soft starting active
p1401.1 [D]
1 = Flux setpoint differentiation active
02
p1401.2 [D]
1 = Flux build-up control active
03
p1401.3 [D]
1 = Flux characteristic load-dependent
06
p1401.6 [D]
1 = Quick magnetizing
07
p1401.7 [D]
1 = Precontrol speed limitation
08
p1401.8 [D]
1 = Speed limiting controller With M_limits
... Reserved
13
p1401.13 [D]
1 = Precontrol characteristic (PESM)
14
p1401.14 [D]
1 = Efficiency optimization active
... Reserved
30
p1401.30 [D]
1 = Speed-dependent flux (parabolic characteristic)
Bit No. Meaning
[6723.6], [6838.5]
[6722.5], [6837.5], [6850.6]
[6640.6]
09
p1401.9 [D]
1 = Dynamic load-dependent flux boost
10
p1401.10 [D]
1 = Flux boost low speed
[6722.4], [6837.4]
[6722.5], [6723.5], [6837.4]
[6790.3], [6834.3]
[6790.3], [6834.3]
[6790.5], [6834.5]
[6851.7]
Flux control configuration
p1401 [D]
Reserved
Figure14-133 6491 - Flux control conguration
Functions
14.10Closed-loop drive control
SINAMICS G220 converter
532 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB