- 2501 -
1
Internal control/status words
Control word, sequence control
© Siemens AG
2 3 4 5 6 7 8
V6.02.00
Reserved
Bit No. Meaning
r0898
r0898.0..14
Control word sequence
control
r0898.0
r0898.1
r0898.2
r0898.31 = Enable operation
r0898.41 = Enable ramp-function generator
r0898.51 = Continue ramp-function generator
r0898.61 = Enable speed setpoint
r0898.71 = Command open brake
r0898.81 = Jog 1
r0898.91 = Jog 2
r0898.101 = Master control by PLC
r0898.121 = Enable speed controller
r0898.141 = Command close brake
01
00
02
03
05
06
07
08
10
11
12
14
13
04
09
15
Reserved
Reserved
c0858 [C]
(0)
Unconditionally close holding brake
c0844 [C]
(1)
No coast-down / coast-down
(OFF2) signal 1
c0840 [C]
(0)
ON / OFF (OFF1)
c0856 [C]
(1)
Enable speed controller
c0854 [C]
(1)
Control by PLC/no control by
PLC
c1056 [C]
(0)
Jog bit 1
c1055 [C]
(0)
Jog bit 0
c0855 [C]
(0)
Unconditionally release holding brake
c1142 [C]
(1)
Enable setpoint/inhibit setpoint
c1141 [C]
(1)
Continue ramp-function generator/
freeze ramp-function generator
c1140 [C]
(1)
Enable ramp-function generator/
inhibit ramp-function generator
c0852 [C]
(1)
Enable operation/inhibit operation
&
&
c0845 [C]
(1)
No coast-down / coast-
down (OFF2) signal 2
c0848 [C]
(1)
No Quick Stop / Quick Stop
(OFF3) signal 1
c0849 [C]
(1)
No Quick Stop / Quick Stop
(OFF3) signal 2
<3>
[2512.2]
<1>
<1>
<1>
<1>
<1>
<1>
<1>
<1>
<1>
<1>
<1>
<1>
<2>
[2512.2]
[2512.2]
[2512.2]
[2512.2], [3060.6],
[3070.7], [3080.5]
[2512.2], [3060.6],
[3070.7]
[2512.2], [3060.1],
[3070.1], [3080.4]
[2701.4]
[2512.2], [3030.6]
[2512.2], [3030.6]
[2512.2]
[2701.4], [6060.4]
PROFIdrive-Bit
= ON
0 = OFF1 active
1 = Operating condition, no coast down active (OFF2 inactive)
0 = OFF2 active
1 = Operating condition, no quick stop active (OFF3 inactive)
0 = OFF3 active
Specified from the HMI device when master control is retrieved
<3>
<2>
<1>
PROFIdrive interconnection:
For PROFIdrive standard telegrams, these inputs are connected with PROFIdrive-STW1 [2415]. Only relevant for CDS0.
Bit 10 in STW1 must be set to ensure that the drive accepts the process data.
<1>
<2>
Figure14-163 2501 - Control word sequence control
Functions
14.11Drive functions
SINAMICS G220 converter
566 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB