- 2503 -
1
Internal control/status words
Status word, sequence control
© Siemens AG
2 3 4 5 6 7 8
V6.02.00
Reserved
Bit No. Meaning
r0899
r0899.0..13
Status word sequence
control
r0899.31 = Jog active
r0899.41 = No coasting active OFF2 inactive
r0899.51 = No Quick Stop active OFF3 inactive
r0899.61 = Switching on inhibited active
r0899.71 = Drive ready
r0899.81 = Controller enable
r0899.91 = Control request
r0899.111 = Pulses enabled
r0899.121 = Open holding brake
r0899.131 = Command close holding brake
01
00
02
03
05
06
07
08
10
11
12
14
13
04
09
15
Reserved
Reserved
PROFIdrive-Bit
<1> The drive is ready to accept data.
r0899.21 = Operation enabled
r0899.11 = Ready
r0899.01 = Ready for switching on
[2510.2], [2701.1]
[2510.2], [2701.1]
[2510.2]
[2510.2]
[2510.2]
[2510.2]
[2510.2]
[2510.2]
≥1
&
c0845 [C]
(1)
No coast-down / coast-down
(OFF2) signal 2
c0849 [C]
(1)
No Quick Stop / Quick Stop
(OFF3) signal 2
OFF1
OFF2
OFF3
<1>
Enable internal
missing or fault
with this reaction
Bit 9 = 1 --> Ready to exchange
process data
[2701.8]
[2701.8]
[2610]
[2610]
[2610]
[2610]
[2610]
[2610]
[2610]
[2610]
[2610]
c0864
(13863.0)
Infeed
operation
Only for Clean Power infeed.
Figure14-164 2503 - Status word sequence control
Functions
14.11Drive functions
SINAMICS G220 converter