- 2610 -
1
Internal control/status words
Sequence control - Sequencer
© Siemens AG
2 3 4 5 6 7 8
V6.02.00
<7>
p0857 … p0861
ZSWA.00/01/02 = 1
ZSWA.11 = 1, ZSWA.06 = 0
ZSWA.06 = 1, ZSWA.11 = 0
ZSWA.00/01/02 = 0
ZSWA.00 = 1, ZSWA.11 = 0
ZSWA.00/01 = 1, ZSWA.11 = 0
ZSWA.02/06 = 0
&
&
<5>
[2634]
<2>
<7>
<1>
S1: Switching on inhibited
S2: Ready for switching on
Pulses inhibited
Main contactor is OPEN
Wait for power-up or jog
POWER ON
S3: Ready for operation
Wait for "Enable operation"
S4: Operation
No jog operation: Setpoints enabled
Pulses enabled
Controller enabled
<3>
"0 = Coast Stop" (STWA.01)
"0 = Quick Stop" (STWA.02)
r0046.8 safety enable missing
"0 = OFF"
Jog 1
Jog 2
"0 = OFF"
Jog 1
Jog 2
Enable operation
(STWA.03)
1
Enable operation (STWA.03)
De-magnetization completed
(r0046.27 = 0)
Encoder ready <6>
1
<5>
[2634]
<3>
"0 = Coast Stop" (STWA.01)
r0046.8 safety enable missing
OFF2 (has priority over jogging)
OFF3 (has priority over jogging)
&
r0863.1
1 = Energize
contactor
c0870
(0)
Close main
contactor
VDC charged
No PM_fault
r0863.0
1 = Precharging
completed
<5>
[2634]
<3>
"0 = Coast Stop" (STWA.01)
"0 = Quick Stop" (STWA.02)
r0046.8 safety enable missing
&
"0 = Coast Stop" (STWA.01)
"0 = Quick Stop" (STWA.02)
"0 = OFF" (STWA.00)
<5>
[2634]
r0046.8 safety enable missing
<3>
"Commissioning completed"
<5>
<4>
<3>
<2>
<1> POWER ON = 24 V electronics supply OFF --> ON or RESET.
The sequence control is implemented according to the PROFIdrive profile.
These control commands can also be triggered by a fault response.
The parameters p1226, p1227 and p1228 influence this status.
Only if "Safety Integrated" is active.
STWA.xx = control word, sequence control, bit xx (r0898) [2501]; ZSWA.xx = status word, sequence control bit xx (r0899) [2503].
<6> Only for operation with encoder.
2000.00 µs
. . .
&
Fault with OFF1- or
OFF3 response
From all states
Enable operation
(STWA.03)
Pulse enable HW
Drive at standstill
ZSWA.00/01 = 1
ZSWA.11 = 1
ZSWA.02/06 = 0
& &
ZSWA.00/01 = 1
ZSWA.11 = 1
ZSWA.02/06 = 0
1
"0 = OFF"
No jog
operation
S5a: Ramp stop
Bring the drive to n 0 along
the ramp-function generator,
then inhibit the pulses
1
Jog 1
Jog 2
<4>
<4>
Jog 1
Jog 2
Jog operation
r0899.8
1 = Controller enable
[2503.3]
S4: Operation
S5a: Ramp stop
S5b: Quick Stop
S5c: Jogging -
down ramp
Bring the drive to n 0 along
the ramp-function generator,
then inhibit the pulses
S5c: Jogging -
down ramp
ZSWA.00/01 = 1
ZSWA.11 = 1
ZSWA.02/06 = 0
<4>
Bring the drive to n 0 along
the ramp-function generator,
then inhibit the pulses
S5b: Quick Stop
&
Enable operation
(STWA.03)
Pulse enable HW
Drive at standstill
&
1
Enable operation
(STWA.03)
Pulse enable HW
Drive at standstill
&
"0 = Quick Stop"
(STWA.02)
"0 = Coast Stop"
(STWA.01)
r0046.8 safety
enable missing
<5>
[2634]
<3>
Missing enable
signals (r0046)
[2634]
F07300...F07802
F06000
Faults
1
1
1
1
c0864
(13863.0)
Infeed
operation
&
Only for Clean Power infeed.
Figure14-165 2610 - Sequence control - sequencer
Functions
14.11Drive functions
SINAMICS G220 converter
568 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB