- 2634 -
1
Internal control/status words
Sequence control - Missing enable signals, line contactor control
© Siemens AG
2 3 4 5 6 7 8
V6.02.00
Bit No. Meaning
r0046
r0046.0..31
Missing enable signal
r0046.91 = Infeed enable missing
r0046.111 = Ramp-function generator start missing
r0046.151 = QuickStop enable missing
r0046.171 = OFF2 enable internal missing
r0046.251 = Function bypass active
r0046.271 = De-magnetizing not completed
r0046.311 = Jog setpoint active
03
01
05
07
11
13
15
17
21
23
25
29
27
09
19
31
r0046.01 = OFF1 enable missing
r0046.11 = OFF2 enable missing
r0046.21 = OFF3 enable missing
r0046.31 = Operation enable missing
r0046.51 = STOP2 enable missing
r0046.81 = Safety enable missing
r0046.101 = Ramp-function generator enable missing
r0046.121 = Speed setpoint enable missing
r0046.261 = Drive inactive or not operational
02
00
04
06
10
12
14
16
20
22
24
28
26
08
18
30
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
r0046.41 = Armature short-circuit / DC braking enable missing
Reserved
Reserved
r0046.161 = OFF1 enable internal missing
r0046.181 = OFF3 enable internal missing
r0046.191 = Pulse enable internal missing
r0046.201 = Armature short-circuit/DC braking internal enable missing
r0046.211 = STOP2 enable internal missing
r0046.281 = Brake open missing
r0046.301 = Speed controller enable missing
1
1
+24 V
T
&
DI
&
1
0
2000.00 µs
[2610.2]
DO
1
c0870
(0)
Close main contactor
Line contactor
control from
sequence control
r0863
r0863.1
1 = Energize contactor
c0860
(863.1)
Line contactor
feedback signal
Line contactor monitoring
time [ms]
p0861 (100)
Fault with OFF3
response
0 = Internal quick stop
1 = Internal RFG enable
[3020.5]
[3060.1]
[3060.4]
[3070.1]
[3070.4]
[3060.1]
[3070.1]
F07300
"Line contactor
feedback signal
missing"
Operating monitoring
Time monitoring
ON/OFF monitoring
Line
Power unit
Figure14-166 2634 - Sequence control - missing data
Functions
14.11Drive functions
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 569