- 7958 -
1
Technology controller
Closed-loop control, vector (part 2)
© Siemens AG
2 3 4 5 6 7 8
V6.02.00
<2>
<3>
+
+
r2273
Technology controller
system deviation [%]
<1>
[7957.8]
r1150
Ramp-function generator speed
setpoint at the output [rpm]
c2286 [C]
(56.13)
Hold technology
controller integrator
c2289 [C]
(0.00)
Technology controller precontrol signal [%]
r0052
r0052.2
1 = Operation enabled
c2200 [C]
(0)
Technology controller enable
Hold techn. controller I component for
n_skip threshold value [%]
p2339 (2.00)
1
r2349
r2349.0
1 = Technology controller deactivated
c2297 [C]
(1084)
Technology controller
maximum limiting
c2298 [C]
(2292)
Technology controller
minimum limiting
c2299 [C]
(0.00)
Technology controller
limit offset [%]
r1084
Positive speed limit effective [rpm]
Technology controller maximum limiting
-200.00 ... 200.00 [%]
p2291 (100.00)
r1087
Negative speed limit effective [rpm]
Technology controller minimum limiting
-200.00 ... 200.00 [%]
p2292 (0.00)
+
+
Technology controller ramp-
up/ramp-down time [s]
p2293 (1.00)
c2290 [C]
(1)
Technology controller limiting enable
r2349
r2349.13
1 = Technology controller limiting enable
r2349
r2349.1
1 = Technology controller limited
r2349.10 1 = Technology controller output at the minimum
r2349.11 1 = Technology controller output at the maximum
Technology controller output scaling
-100.00 ... 100.00 [%]
p2295 (100.00)
c2296 [C]
(2295)
Technology controller output scaling
10 s
Technology controller fixed value 15
-200.00 ... 200.00 [%]
p2215 [D] (150.00)
r2344
Technology controller last speed setpoint (smoothed) [%]
Technology controller fault response
p2345 (0)
0
1
2
0
r2294
Technology controller
output signal [%]
r2349.12
1 = Fault response active
Technology controller output
signal starting value [%]
p2302 (0.00)
0
1
<6>
<1>
<5>
<4>
The start value p2302 is only used in mode p2251 = 0. After enable of technology controller the start value is present as long as the RFG output reaches this value.
<3>
I component stop, only when r2273 and r2294 in same direction.
<4>
Recommendation for p2251 = 1: c2299 connected to r1150.
<5> Signal = 0 --> factor = 0, when setpoint from external operating tool or operator panel.
r2349.12 = 1, if p2345 > 0 and actual value limited and start value p2302 not active.
<2>
p2251 = 0: I component is stopped, when r2294 is below the minimum speed or within a suppression bandwidth.
<6>
[7959.8]
Tn
[7959.8]
Kp
[2513.2]
Figure14-258 7958 – Closed-loop control, vector (part2)
Functions
14.13Technology functions
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 719