Technology controller
Kp-/Tn-adaptation and Kp-/Tn-selection
© Siemens AG
2 3 4 5 6 7 8
V6.02.00
c2310
(0.00)
Technology controller
Kp adaptation input
value [%]
c2317
(0.00)
Technology controller
Tn adaptation input
value [%]
[7958.3]
[7958.3]
Technology controller Tn adaptation lower value
0.000 ... 60.000 [s]
p2319 (10.000)
Technology controller Tn adaptation upper value
0.000 ... 60.000 [s]
p2318 (3.000)
Technology controller Kp adaptation upper value
0.000 ... 1000.000
p2312 (10.000)
Technology controller Kp adaptation lower value
0.000 ... 1000.000
p2311 (1.000)
Technology controller Tn
adaptation lower starting point
0.00 ... 400.00 [%]
p2320 (0.00)
Technology controller Tn
adaptation upper starting point
0.00 ... 400.00 [%]
p2321 (100.00)
Technology controller Kp
adaptation lower starting point
0.00 ... 400.00 [%]
p2313 (0.00)
Technology controller Kp adaptation upper
starting point
0.00 ... 400.00 [%]
p2314 (100.00)
r2322
Technology controller
Tn adaptation output [s]
r2316
Technology controller,
Kp adaptation output
c2315
(100.00)
Technology controller Kp
adaptation scaling [%]
1
0
1 = Activate Kp adaptation
p2252.7 (0)
1 = Activate Tn adaptation
p2252.8 (0)
1
0
Technology controller proportional gain
0.000 ... 1000.000
p2280 (1.000)
Technology controller integral time
0.000 ... 10000.000 [s]
p2285 (30.000)
Tn
Kp
<1> For deactivated adaptation the P and I component can be disabled by entering a zero.
<1>
<1>
Figure14-259 7959 – Kp/Tn adaptation and Kp/Tn selection