PR-MAINT (Maintenance Processor)
Issue 4 May 2002
10-1389555-233-123
MTP Outpulse Relay Test (#102)
This test is a nondestructive test. The test validates the correct operation of the
remote access CO trunk used by INADS. The MTP first goes off-hook, then
on-hook on this trunk. If the loop current is detected, the test passes. This test is
not allowed if the remote access line is in use.
10106 FAIL The Maintenance/Tape Processor was reset, but it
responded with a NOT PASS status, indicating that it did not
pass initialization correctly. The MTP is not functioning
correctly. The system should continue to function, but it will
not have the ability to save translation to tape, or to read tape
if the system needs to be rebooted. Environmental monitoring
is lost, as is communication with the Standby Processor.
1. Retry the command at 1-minute intervals a maximum of
5 times.
2. If test continues to fail, replace the Processor circuit
pack.
PASS The Maintenance/Tape Processor was reset, and it passed
initialization correctly. The other MTP tests should be
examined to verify that the MTP is functioning correctly.
1. Enter test processor a/b and verify that the MTP is
functioning correctly.
Table 10-515. TEST #101 MTP Reset Test Continued
Error
Code
Te s t
Result Description/Recommendation
Continued on next page