Maintenance Object Repair Procedures
555-233-123
10-1628 Issue 4 May 2002
Tape Unit Aux Data/Error Codes Tables
Table 10-603. Table A: Tape Unit Aux Data Table
Aux Data/
Error Codes Explanation Strategy
9002 Internal system error. Escalate the problem.
9003 Hardware not responding. 1. Follow the instructions provided in the
‘‘Tape Maintenance and Repair
Procedures’’ section.
9004 9005 Internal system error. Escalate the problem.
9009 Operation timed out. 1. Follow the instructions provided in the
‘‘Tape Maintenance and Repair
Procedures’’ section.
9010 Hardware not responding.
9011 Internal system error. Escalate the problem.
9012 Tape already in use. 1. If the Tape Unit is in use (that is, the yellow
LED on the tape drive is on and there is
tape cartridge motion), wait until the first
request is complete. If there does not
appear to be tape motion and/or the
yellow LED on the tape drive is not on,
go to next step.
2. Retry the test tape command at 1-minute
intervals a maximum of 5 times.
9013 Tape drive self-test failed. 1. Follow the instructions provided in the
‘‘Tape Maintenance and Repair
Procedures’’ section.
9015 Test detected hardware failure.
9017 Could NOT reset the tape
drive.
9020
!
WARNING:
The tape cartridge is
starting to wear, but it is
still functional.
9023 Write-protected tape. 1. Disable the write-protect switch on the tape
cartridge.
2. Check the power by performing Step 1 of
the ‘‘Tape Maintenance and Repair
Procedures’’ section.
Continued on next page