Signals and monitoring functions
Monitoring functions (part 1)
© Siemens AG
2 3 4 5 6 7 8
V6.02.00
r2169
Actual speed smoothed
signals [rpm]
r1119
Ramp-function generator
setpoint at the input [rpm]
r0070
Actual DC link voltage [V]
r0072
Output voltage [Vrms]
DC link voltage threshold value
0 ... 2000 [V]
p2172 [D] (800)
Torque actual value filter time constant
0 ... 1000000 [ms]
p3233 [D] (100)
Current threshold value
0.00 ... 10000.00 [Arms]
p2170 [D] (0.00)
Output load identification current limit
0.00 ... 1000.00 [Arms]
p2179 [D] (0.00)
Threshold for zero speed detection
0.00 ... 210000.00 [rpm]
p1226 [D] (20.00)
Pulse cancellation delay time
0.000 ... 299.000 [s]
p1228 [D] (0.000)
DC link voltage comparison
delay time
0 ... 10000 [ms]
p2173 [D] (10)
Current threshold value
reached delay time
0 ... 10000 [ms]
p2171 [D] (10)
Output load detection delay time
0 ... 10000 [ms]
p2180 [D] (2000)
r2197
r2197.0
1 = |n_act| <= n_min p1080
r2197
r2197.4
1 = |n_act| >= n_set
r2197
r2197.5
1 = |n_act| <= n_standstill p1226
r2197
r2197.9
1 = Vdc_act <= Vdc_threshold value p2172
r2197
r2197.10
1 = Vdc_act > Vdc_threshold value p2172
r2197
r2197.8
1 = I_act >= I_threshold value p2170
r2198
r2198.8
1 = |I_act| < I_threshold value p2170
r2197
r2197.11
1 = Output load is not present
1
0
-1
1
0
1
–
+
1
0
0
1
0
1
T 0
0
1
1
0
T 0
1
0
&
T 0
0 T
1
T 0
0 T
Hysteresis speed 3
0.00 ... 300.00 [rpm]
p2150 [D] (2.00)
Minimum speed
0.000 ... 19500.000 [rpm]
p1080 [D] (0.000)
0
0
0
A07929
p0504 = 2: Dynamic Drive Control (DDC)
p0504 = 1: Standard Drive Control (SDC)
[8010.3]
[3051.8]
[6730.1], [6731.1], [6792.1]
[6841.1], [6842.1], [6843.1]
[6856.1]
[6715.8]
[6833.8]
[6856.1]
[6730.5], [6731.5], [6792.5]
[6841.5], [6842.5], [6843.5]
[6856.5]
[2534.4]
[2536.4]
[2534.4]
[2534.4]
[2534.4]
[2534.4]
[2534.4]
[2534.4]
Drive: No motor detected
Enable pulses
r0063[0]
Speed actual value
Unsmoothed [rpm]
r0068[0]
Absolute current actual
value Unsmoothed [Arms]
Figure14-217 8022 – Monitoring functions (part1)
Functions
14.11Drive functions
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 647