- 2534 -
1
Internal control/status words
Status word, monitoring functions 1
© Siemens AG
2 3 4 5 6 7 8
V6.02.00
Bit No. Meaning
r2197
r2197.0..13
Status word monitoring 1
r2197.31 = n_act >= 0
r2197.41 = |n_act| >= n_set
r2197.51 = |n_act| <= n_standstill p1226
r2197.61 = |n_act| > n_max
r2197.71 = Speed setpoint - actual value deviation in tolerance t_off
r2197.81 = I_act >= I_threshold value p2170
r2197.91 = Vdc_act <= Vdc_threshold value p2172
r2197.101 = Vdc_act > Vdc_threshold value p2172
r2197.121 = |n_act| > n_max (delayed)
01
00
02
03
05
06
07
08
10
11
12
14
13
04
09
15
r2197.01 = |n_act| <= n_min p1080
r2197.11 = |n_act| <= speed threshold 2 p2155
r2197.21 = |n_act| > speed threshold 2 p2155
r2197.131 = |n_act| > n_max (F07901)
r2197.111 = Output load is not present
Reserved
Reserved
[2511.2]
[2511.2]
[2511.2]
[2511.2]
[2511.2]
[2511.2]
[2511.2]
[2511.2]
[2510.2]
[2510.2]
[2510.2]
[8022.8]
[8010.8]
[8011.8]
[8022.8]
[8022.8]
[8010.8]
[8011.8]
[8022.8]
[8022.8]
[8022.8]
[8022.8]
[8023.8]
[8010.8]
[8023.1]
Figure14-220 2534 - Status word monitoring functions 1
Functions
14.11Drive functions
SINAMICS G220 converter
650 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB