- 2536 -
1
Internal control/status words
Status word, monitoring functions 2
© Siemens AG
2 3 4 5 6 7 8
V6.02.00
Bit No. Meaning
r2198
r2198.0..13
Status word monitoring 2
r2198.31 = |n_act| > speed threshold value 6
r2198.41 = |n_set| < p2161
r2198.51 = n_set > 0
r2198.61 = Motor blocked
r2198.71 = Motor stalled
r2198.81 = |I_act| < I_threshold value p2170
r2198.91 = |M_act| > torque threshold value 1 and n_set reached
r2198.101 = |M_set| < torque threshold value 1
r2198.121 = Load in the fault range
01
00
02
03
05
06
07
08
10
11
12
14
13
04
09
15
r2198.01 = |n_act| <= speed threshold value 5
r2198.11 = |n_act| > speed threshold value 5
r2198.21 = |n_act| <= speed threshold value 6
r2198.131 = |M_act| > torque threshold value 1
r2198.111 = Load in the alarm range
Reserved
Reserved
[8023.8]
[8023.8]
[8023.8]
[8011.8]
[8011.8]
[8015.8]
[8015.8]
[8022.8]
[8023.8]
[8012.8]
[8013.8]
[8013.8]
[8023.8]
[8023.8]
Figure14-221 2536 - Status word monitoring functions 2
Functions
14.11Drive functions
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB 651