- 2854 -
1
Safety Integrated
Control signals safe motion monitoring functions (part 1)
© Siemens AG
2 3 4 5 6 7 8
V6.02.00
p9500
c10022
(10071.0)
SI STO input terminal
r10075
r10075.0
1 = Deselect STO
c10023
(1)
SI SS1 input terminal
1
0
1
0
1 = Control via F-DI Enable
p9603.0 (1)
1 = Control via PROFIsafe Enable
p9603.1 (0)
1
1
1
0
1
0
1
1
1
0
1 = Enable STO Enable
p9604.0 (1)
1
0
1
1
1
1
1
0
1 = Enable SS1 Enable
p9604.2 (0)
1
0
1
1
1
1
r10075
r10075.1
1 = Deselect SS1
c10026
(1)
SI SLS input terminal
1
0
1
0
1
1
1
0
1 = Enable SLS Enable
p9604.8 (0)
1
0
1
1
1
1
r10075
r10075.4
1 = Deselect SLS
c10027
(0)
SI SLS limit bit 0 input terminal
1
0
1
0
1
1
1
0
1
0
1
1
r10075
r10075.9
1 = Select SLS bit 0 Set
c10028
(0)
SI SLS limit bit 1 input terminal
1
0
1
0
1
1
1
0
1
0
1
1
r10075
r10075.10
1 = Select SLS bit 1 Set
&
&
&
[2856.1]
[2856.1]
[2856.1]
[2856.1]
[2856.1]
&
&
r9720
r9720.0
1 = Deselect STO
r9720
r9720.1
1 = Deselect SS1
r9720
r9720.4
1 = Deselect SLS
r9720
r9720.9
1 = Select SLS bit 0
Set
r9720
r9720.10
1 = Select SLS bit 1
Set
r10356
r10356.1
1 = Selection via PROFIsafe
r10353
r10353.1
1 = Selection via PROFIsafe
r10352
r10352.1
1 = Selection via PROFIsafe
r10352
r10352.0
1 = Selection via F-DI
r10353
r10353.0
1 = Selection via F-DI
r10356
r10356.0
1 = Selection via F-DI
<1> Only F-DI 0 can be used for control via PROFIsafe. For control via PROFIsafe, the fail-safe digital output can only be interconnected with STO (Safe Torque Off) / SS1 (Safe Stop 1).
<1>
Figure14-247 2854 – Control signals safe motion monitoring function (part1)
Functions
14.12Safety Integrated
SINAMICS G220 converter
700 Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB