System Utilities
CLI L2P
Release
7.0
05/2011
trap
Configures the sending of traps concerning the signal contact.
enable enables sending traps,
disable disables sending traps.
4.11.26temperature
This command configures the lower and upper temperature limit for the
device. If these limits are exceeded, a trap is sent. The unit for the
temperature limit is °C (Celsius), the minimum value is -99, the maximum
value is 99. The default for the lower limit is 0, for the upper limit, it is 70.
Note: To give the temperature in Fahrenheit, use the suffix f.
Note: The command is available for RS20/RS30/RS40, MS20/MS30,
RSR20/RSR30, MACH100, MACH 1000, PowerMICE, MACH 4000 and
OCTOPUS devices.
Format
temperature {lower-limit|upper-limit} <temperature
value> [c|f]
Mode
Global Config
lower-limit
Configure the lower temperature limit.
upper-limit
Configure the upper temperature limit.