RX2540 M2 Upgrade and Maintenance Manual 463
Front panel and external front connectors
Ê Store your server’s system information on the Chassis ID EPROM
integrated into the front panel board. For further information on how to obtain
and use the ChassisId_Prom Tool, refer to section "Using the Chassis ID
Prom Tool" on page 123.
Ê "Enabling SVOM boot watchdog functionality" on page 114
Ê "Resuming BitLocker functionality" on page 120
13.2 Front panel board 3.5-inch versions
13.2.1 Replacing the front panel board
Note on system information backup / restore
I The front panel module contains the Chassis ID EPROM that contains
system information like server name and model, housing type, serial
number and manufacturing data.
To avoid the loss of non-default settings when replacing the system
board, a backup copy of important system configuration data is
automatically stored from the system board NVRAM to the Chassis ID
EPROM. After replacing the system board the backup data is restored
from the Chassis ID board to the new system board.
V CAUTION!
For that reason the front panel module and system board must not be
replaced simultaneously! In this case, restoring the system configuration
data on the system board would fail.
13.2.1.1 Preliminary steps
Ê "Suspending BitLocker functionality" on page 95
Field Replaceable Unit
(FRU)
Hardware: 10 minutes
Software: 5 minutes
Tools: flat screw driver
nut driver 5 mm