Frequently-used parameters (simple mode parameters)
106
BASIC OPERATION
 Initial value for the FR-A820-00077(0.75K) or lower and FR-A840-00038(0.75K) or lower.
 Initial value for the FR-A820-00105(1.5K) to FR-A820-00250(3.7K) and the FR-A840-00052(1.5K) to FR-A840-00126(3.7K).
 Initial value for the FR-A820-00340(5.5K), FR-A820-00490(7.5K), FR-A840-00170(5.5K), and FR-A840-00250(7.5K).
 Initial value for the FR-A820-00630(11K) to FR-A820-03160(55K), FR-A840-00310(11K) to FR-A840-01800(55K).
 Initial value for the FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher.
 For the FR-A820-03160(55K) or lower and FR-A840-01800(55K) or lower.
 For the FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher.
 The initial value for the FR-A820-00077(0.75K) or lower and FR-A840-00038(0.75K) or lower is set to the 85% of the rated inverter current.
 Initial value for the FR-A820-00490(7.5K) or lower and FR-A840-00250(7.5K) or lower.
 Initial value for the FR-A820-00630(11K) or higher and FR-A840-00310(11K) or higher.
 FM denotes the initial value for the FM type inverter that has the terminal FM, and CA denotes the initial value for the CA type inverter that has
the terminal CA.
160 E440
User group read
selection
1 0 0, 1, 9999
Restricts the parameters that are read by the
operation panel and parameter unit.
275
998 E430
PM parameter
initialization
10
0, 3003,
3103, 8009,
8109, 9009,
9109
Selects the PM sensorless vector control and
set the parameters that are required to drive an
PM motor.
172
999 E431
Automatic
parameter setting
1 9999
1, 2, 10, 11,
12, 13, 20,
21, 30, 31,
9999
Changes parameter settings as a batch. The
target parameters include communication
parameters for the Mitsubishi's human
machine interface (GOT) connection and the
parameters for the rated frequency settings of
50 Hz/60 Hz.
271
Pr.
Pr.
group
Name Unit
Initial value

Range Application
Refer
to
page
FM CA

Table of Contents