EasyManua.ls Logo

Mitsubishi FR-A800

Mitsubishi FR-A800
746 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Basic operation procedure (PU operation)
BASIC OPERATION
111
4
4.5.5 Using an analog signal (current input) to give a
frequency command
POINTPOINT
Use the operation panel (FR-DU08) ( or) to give a start command.
Use the outputs from the current signal source (4 to 20 mA) to give a frequency command (by connecting it across terminals
4 and 5 (current input)).
Turn ON the AU signal.
•Set Pr.79 Operation mode selection ="4" (External/PU combination operation mode 2).
[Connection diagram]
NOTE
Pr.184 AU terminal function selection must be set to "4" (AU signal) (initial value).
To change the frequency (60 Hz) at the maximum current input (initial value 20 mA), adjust Pr.126 Terminal 4 frequency
setting gain frequency.
To change the frequency (0 Hz) at the minimum current input (initial value 4 mA), adjust the calibration parameter C5
Terminal 4 frequency setting bias frequency.
Parameters referred to
Pr.7 Acceleration time, Pr.8 Deceleration time page 285
Pr.79 Operation mode selection page 306
Pr.126 Terminal 4 frequency setting gain frequency page 415
Pr.184 AU terminal function selection? page 430
C5(Pr.904) Terminal 4 frequency setting bias frequency page 415
Operation example Operate at 60 Hz.
Operation
1.
Screen at power-ON
The monitor display appears.
2.
Changing the operation mode
Set "4" in
Pr.79. [PU] and [EXT] indicators are on. (For setting value change, refer to page 101.)
3.
Terminal 4 input selection
Turn ON the terminal 4 input selection signal (AU). Input to the terminal 4 is enabled.
4.
Start
Press or . [FWD] or [REV] flickers as no frequency command is given.
5.
Acceleration constant speed
Input 20 mA. The frequency value on the indication increases in Pr.7 Acceleration time, and " " (60.00 Hz)
appears.
6.
Deceleration
Input 4 mA or less.The frequency value on the indication decreases in Pr.8 Deceleration time, and the motor stops rotating
with " " (0.00 Hz) displayed. [FWD] or [REV] indicator flickers.
7.
Stop
Press . [FWD] or [REV] indicator turns OFF.
Inverter
Operation panel
(FR-DU08)
Current signal
source
(4 to 20mADC)
5(-)
4(+)
SD
AU
A
U signal

Table of Contents

Related product manuals