(E) Environment setting parameters
PARAMETERS
261
5
GROUP
E
Reset limit function (P.E107)
When P. E1 0 7 = "1" or Pr.75 = any of "100 to 103 and 114 to 117", if an electronic thermal O/L relay or an overcurrent
protective function (E.THM, E.THT, E.OC[]) is activated while one of them has been already activated within 3 minutes, the
inverter will not accept any reset command (RES signal, etc.) for about 3 minutes from the second activation.
The reset limit function is available with the FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher.
NOTE
Resetting the inverter power (turning OFF the control power) will clear the accumulated thermal value.
When the retry function is set enabled (Pr.67 Number of retries at fault occurrence "0"), the reset limit function is
disabled.
???????
Parameters referred to
Pr.67 Number of retries at fault occurrence page 343
Pr.79 Operation mode selection page 306
Pr.250 Stop selection page 613
Pr.551 PU mode operation command source selection page 316
5.7.3 PU display language selection
5.7.4 Buzzer control
NOTE
When with buzzer is set, the buzzer sounds if an inverter fault occurs.
5.7.5 PU contrast adjustment
The above parameter is displayed as a simple mode parameter only when the LCD operation panel (FR-LU08) and the parameter unit (FR-
PU07) is connected.
Caution
Do not perform a reset while a start signal is being input. Doing so will cause a sudden start of the
motor, which is dangerous.
The display language of the parameter unit (FR-PU07) can be selected.
Pr. Name Initial value Setting range Description
145
E103
PU display language
selection
1
0 Japanese
1 English
2German
3 French
4 Spanish
5Italian
6Swedish
7Finnish
The buzzer can be set to "beep" when the keys of the operation panel and the parameter unit are operated.
Pr. Name Initial value Setting range Description
990
E104
PU buzzer control
1
0 Without buzzer
1 With buzzer
Contrast adjustment of the LCD of the LCD operation panel (FR-LU08) and the parameter unit (FR-PU07) can be
performed.
Decreasing the setting value lowers the contrast.
Pr. Name Initial value Setting range Description
991
E105
PU contrast adjustment
58 0 to 63 0: Low 63: High