EasyManua.ls Logo

Mitsubishi FR-A800

Mitsubishi FR-A800
746 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Measurement of main circuit voltages, currents and powers
PRECAUTIONS FOR MAINTENANCE AND INSPECTION
687
7
7.2.7 Measurement of inverter output frequency
In the initial setting of the FM-type inverter, a pulse train proportional to the output frequency is output across the pulse train
output terminals FM and SD of the inverter. This pulse train output can be counted by a frequency counter, or a meter
(moving-coil type voltmeter) can be used to read the mean value of the pulse train output voltage. When a meter is used to
measure the output frequency, approximately 5 VDC is indicated at the maximum frequency.
For detailed specifications of the pulse train output terminal FM, refer to page 375.
In the initial setting of the CA-type inverter, a pulse train proportional to the output frequency is output across the analog
current output terminals CA and 5 of the inverter. Measure the current using an ammeter or tester.
For detailed specifications of the analog current output terminal CA, refer to page 377.
7.2.8 Insulation resistance test using megger
For the inverter, conduct the insulation resistance test on the main circuit only as shown below and do not perform the test
on the control circuit. (Use a 500 VDC megger.)
NOTE
Before performing the insulation resistance test on the external circuit, disconnect the cables from all terminals of the inverter
so that the test voltage is not applied to the inverter.
For the continuity test of the control circuit, use a tester (high resistance range) and do not use the megger or buzzer.
7.2.9 Pressure test
Do not conduct a pressure test. Deterioration may occur.
U
V
W
Inverter
500VDC
megger
Power
supply
IM
Motor
R/L1
S/L2
T/L3

Table of Contents

Related product manuals