(G) Control parameters
PARAMETERS
615
5
GROUP
G
Details of the setting value
• FR-A820-03160(55K) or lower, FR-A840-01800(55K) or lower
• FR-A820-03800(75K) or higher, FR-A840-02160(75K) or higher
• FR-A842-07700(315K) or higher
For the FR-A820-00490(7.5K) or lower and FR-A840-00250(7.5K) or lower.
For the FR-A820-00630(11K) or higher, and FR-A840-00310(11K) or higher.
Built-in brake is installed on FR-A820-00490(7.5K) or lower, FR-A840-00250(7.5K) or lower.
While the power is supplied only to the control circuit with Pr.30 = "100 or higher", the inverter reset is not performed when the power is supplied to the
main circuit.
NOTE
• For the use of a brake resistor other than FR-ABR, contact your sales representative.
When using built-in brake resistor, brake unit (FR-BU2, BU, FR-BU) (FR-
A820-03160(55K) or lower, FR-A840-01800(55K) or lower)
• When using the built-in brake, using FR-BU2 in combination with GZG/GRZG/FR-BR, or using BU or FR-BU, set Pr.30 = "0
(initial value), 10, 20, 100, 110, 120". Setting of Pr.70 will become disabled.
At this time, the regenerative brake duty is as follows.
• FR-A820-00250(3.7K) or lower................................3%
• FR-A820-00340(5.5K), FR-A820-00490(7.5K) ........ 2%
• FR-A840-00250(7.5K) or lower................................2%
• Other than above .....................................................0% (without built-in brake resistor)
NOTE
• The built-in brake resistor is equipped for the FR-A820-00490(7.5K) or lower, and the FR-A840-00250(7.5K) or lower.
Regeneration unit
Power supply
terminals of inverter
Pr.30
Setting
Pr.70
Setting
Remarks
Built-in brake ,
Brake unit
(FR-BU2 (GZG/GRZG/
FR-BR), FR-BU, BU)
R, S, T
0 (initial
value), 100
The regenerative brake duty will be as follows.
• FR-A820-00046(0.4K) to FR-A820-00250(3.7K): 3%
• FR-A820-00340(5.5K), FR-A820-00490(7.5K): 2%
• FR-A840-00023(0.4K) to FR-A840-00250(7.5K): 2%
• Other than above: 0% (without the built-in brake resistor)
P, N 10, 110
R, S, T/P, N 20, 120
High-duty brake resistor
(FR-ABR)
R, S, T 1, 101
10%
6%
FR-ABR can be used with FR-A820-01250(22K) or lower
and FR-A840-00620(22K) or lower.
P, N 11 , 111
R, S, T/P, N 21, 121
High power factor converter
(FR-HC2),
Power regeneration
common converter (FR-CV)
P, N 2, 102
0%
(initial
value)
Regeneration unit
Power supply
terminals of inverter
Pr.30 Setting Pr.70 Setting
Without regenerative function
R, S, T 0 (initial value), 100
P, N 10, 110
R, S, T/P, N 20, 120
Brake unit (FR-BU2 (MT-BR5))
R, S, T 1, 101
0% (initial value)P, N 11 , 111
R, S, T/P, N 21, 121
Power regeneration converter (MT-RC) R, S, T 1, 101 0% (initial value)
High power factor converter (FR-HC2) P, N 2, 102
Regeneration unit Pr.30 Setting
Without regenerative function (FR-CC2) 10 (initial value), 110
Brake unit
(FR-CC2+FR-BU2 (MT-BR5))
11, 111
High power factor converter (FR-HC2) 2, 102