(N) Operation via communication and its settings
584
PARAMETERS
Preset Single Register (writing of data to holding registers) (H06 or 06)
• The content of the "system environmental variables" and "inverter parameters" assigned to the holding register area (refer
to the register list (page 589)) can be written.
• Query message
• Normal response (Response message)
• Query message setting
• Content of normal response
With a normal response, the content is the same as a to d (including the CRC check) query messages.
In the case of broadcast communication, no response is returned.
NOTE
• With broadcast communication, no response is generated even if a query is executed, so when the next query is made, it
must be made after waiting for the inverter data processing time after the previous query is executed.
a. Slave
Address
b. Function
c. Register
Address
d. Preset Data CRC Check
(8 bits)
H06
(8 bits)
H
(8 bits)
L
(8 bits)
H
(8 bits)
L
(8 bits)
L
(8 bits)
H
(8 bits)
a. Slave
Address
b. Function
c. Register
Address
d. Preset Data CRC Check
(8 bits)
H06
(8 bits)
H
(8 bits)
L
(8 bits)
H
(8 bits)
L
(8 bits)
L
(8 bits)
H
(8 bits)
Message Description
a Slave Address Set the address to send messages to. Setting "0" enables broadcast communication.
b Function Set H06.
c Register Address
Set the address from data is written to the holding register.
Register address = holding register address (decimal) - 40001
For example, when register address 0001 is set, data is written to holding register
address 40002.
d Preset Data Set the data to write to the holding register. Write data is fixed at 2 bytes.
Example) Write 60Hz (H1770) to 40014 (running frequency) of slave address 5 (H05).
Query message
Normal response (Response message)
Same data as query message
Slave
Address
Function Register Address Preset Data CRC Check
H05
(8 bits)
H06
(8 bits)
H00
(8 bits)
H0D
(8 bits)
H17
(8 bits)
H70
(8 bits)
H17
(8 bits)
H99
(8 bits)