EasyManua.ls Logo

Mitsubishi FR-A800

Mitsubishi FR-A800
746 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
(M) Monitor display and monitor output signal
PARAMETERS
359
5
GROUP
M
5.11.2 Monitor indicator selection using operation
panel or via communication
The monitored item to be displayed on the operation panel or the parameter unit can be selected.
Pr. Name Initial value Setting range Description
52
M100
Operation panel main
monitor selection
0
(output
frequency)
0, 5 to 14, 17 to 20,
22 to 35, 38,
40 to 45, 50 to 57, 61, 62,
64, 67, 87 to 98, 100
Select the monitor to be displayed on the
operation panel and parameter unit.
Refer to page 360 for the monitor
description.
774
M101
Operation panel monitor
selection 1
9999
1 to 3, 5 to 14,
17 to 20, 22 to 35, 38,
40 to 45, 50 to 57, 61, 62,
64, 67, 87 to 98, 100,
9999
The output frequency, output current and
output voltage monitor that are displayed
in monitor mode on the operation panel
and parameter unit can be switched to a
specified monitor.
9999: Follows the Pr.52 setting.
775
M102
Operation panel monitor
selection 2
776
M103
Operation panel monitor
selection 3
992
M104
Operation panel setting dial
push monitor selection
0
(Set
frequency)
0 to 3, 5 to 14,
17 to 20, 22 to 35, 38,
40 to 45, 50 to 57, 61, 62,
64, 67, 87 to 98, 100
Select the monitor to be displayed when
the setting dial on the operation panel is
pushed.
170
M020
Watt-hour meter clear
9999
0
Set "0" to clear the watt-hour meter
monitor.
10
Set the maximum value for monitoring via
communication. Set it in the range of 0
and 9999 kWh.
9999
Set the maximum value for monitoring via
communication. Set it in the range of 0
and 65535 kWh.
563
M021
Energization time carrying-
over times
0
(0 to 65535)
(Read-only)
Displays the numbers of times that the
cumulative energization time monitor
exceeded 65535 h. Read-only.
268
M022
Monitor decimal digits
selection
9999
0 Displays as integral value.
1 Displays in 0.1 increments.
9999 No function
891
M023
Cumulative power monitor
digit shifted times
9999
0 to 4
Set the number of times to shift the
cumulative power monitor digit.
The monitor value is clamped at the
maximum value.
9999
No shift
Monitor value is cleared when it exceeds
the maximum value.
171
M030
Operation hour meter clear
9999
0
Set "0" to clear the operation hour
monitor.
9999
The read value is always 9999. Nothing
happens when "9999" is set.
564
M031
Operating time carrying-
over times
0
(0 to 65535)
(Read-only)
Displays the numbers of times that the
operating time monitor exceeded 65535
h. Read-only.
290
M044
Monitor negative output
selection
0 0 to 7
Set the availability of output with a minus
sign for the terminal AM, the operation
panel display, or monitoring via
communication. (Refer to page 368)
1106
M050
Torque monitor filter
9999
0 to 5 s
The filter time constant is selectable for
monitoring of the torque. A larger setting
results in slower response.
9999 0.3 s filter
1107
M051
Running speed monitor
filter
9999
0 to 5 s
The filter time constant is selectable for
monitoring of the running speed. A larger
setting results in slower response.
9999 0.08 s filter
1108
M052
Excitation current monitor
filter
9999
0 to 5 s
The filter time constant is selectable for
monitoring of the motor excitation current.
A larger setting results in slower
response.
9999 0.3 s filter

Table of Contents

Related product manuals