Frequently-used parameters (simple mode parameters)
BASIC OPERATION
105
4
4.4 Frequently-used parameters (simple mode
parameters)
Parameters that are frequently used for the FR-A800 series are grouped as simple mode parameters.
When Pr.160 User group read selection="9999", only the simple mode parameters are displayed.
This section explains about frequently-used parameters.
4.4.1 Simple mode parameter list
For simple variable-speed operation of the inverter, the initial values of the parameters may be used as they are. Set the
necessary parameters to meet the load and operational specifications. Parameter setting, change and check can be
performed from the operation panel (FR-DU08).
POINTPOINT
• Pr.160 User group read selection can narrow down the displayed parameters to only the simple mode parameters. (In the
initial setting, all parameters are displayed.) Set Pr.160 User group read selection as required. (For the parameter change,
refer to page 101.)
Pr.160 setting Description
9999 Displays only the simple mode parameters.
0
(initial value)
Displays simple mode + extended parameters.
1 Displays parameters registered in the user group.
Pr.
Pr.
group
Name Unit
Initial value
Range Application
Refer
to
page
FM CA
0 G000 Torque boost 0.1%
6%
0 to 30%
Set this parameter to obtain a higher starting
torque under V/F control. Also set this when a
loaded motor cannot be driven and the
warning [OL] occurs, then the inverter trips with
[OC1].
597
4%
3%
2%
1%
1 H400 Maximum frequency 0.01 Hz
120 Hz
0 to 120 Hz Sets the upper limit for the output frequency.
34560 Hz
2 H401 Minimum frequency 0.01 Hz 0Hz 0 to 120 Hz Sets the lower limit for the output frequency.
3 G001 Base frequency 0.01 Hz 60 Hz 50 Hz 0 to 590 Hz
Set this parameter when the rated motor
frequency is 50 Hz.
Check the rating plate of the motor.
598
4 D301
Multi-speed setting
(high speed)
0.01 Hz 60 Hz 50 Hz 0 to 590 Hz
Pre-sets the speeds that will be switched
among by terminals.
109,
114,
328
5 D302
Multi-speed setting
(middle speed)
0.01 Hz 30 Hz 0 to 590 Hz
6 D303
Multi-speed setting
(low speed)
0.01 Hz 10 Hz 0 to 590 Hz
7 F010 Acceleration time 0.1 s
5 s
0 to 3600 s Sets the acceleration time.
285
15 s
8 F011 Deceleration time 0.1 s
5 s
0 to 3600 s Sets the deceleration time.
15 s
9
H000
C103
Electronic thermal
O/L relay
0.01 A
Rated inverter
current
0 to 500 A
Protects the motor from heat.
Set the rated motor current.
331
0.1 A
0 to 3600 A
79 D000
Operation mode
selection
1 0 0 to 4, 6, 7
Select the start and frequency command
sources.
306
125 T022
Terminal 2
frequency setting
gain frequency
0.01 Hz 60 Hz 50 Hz 0 to 590 Hz
Allows the frequency at the maximum
potentiometer setting (5 V in the initial setting)
to be changed.
116,
415
126 T042
Terminal 4
frequency setting
gain frequency
0.01 Hz 60 Hz 50 Hz 0 to 590 Hz
Allows the frequency at the maximum current
input (20 mA in the initial setting) to be
changed.
118,