(N) Operation via communication and its settings
580
PARAMETERS
Outline
The Modbus communication protocol was developed by Modicon for programmable controllers.
The Modbus protocol uses exclusive message frames to perform serial communication between a master and slaves.
These exclusive message frames are provided with a feature called "functions" that allows data to be read or written. These
functions can be used to read or write parameters from the inverter, write input commands to the inverter or check the
inverter's operating status, for example. This product classifies the data of each inverter into holding register area (register
address 40001 to 49999). The master can communicate with inverters (for instance,. slaves) by accessing pre-assigned
holding register addresses.
NOTE
There are two serial transmission modes, the ASCII (American Standard Code for Information Interchange) mode and the
RTU (Remote Terminal Unit) mode. However, this product supports only the RTU mode, which transfers 1 byte data (8 bits)
as it is. Also, only communication protocol is defined by the Modbus protocol. Physical layers are not stipulated.
Message format
Data check time
•Query
A message is sent to the slave (for instance, the inverter) having the address specified by the master.
Normal Response
After the query from the master is received, the slave executes the request function, and returns the corresponding normal
response to the master.
Error Response
When an invalid function code, address or data is received by the slave, the error response is returned to the master.
This response is appended with an error code that indicates the reason why the request from the master could not be
executed.
This response cannot be returned for errors, detected by the hardware, frame error and CRC check error.
Broadcast
The master can broadcast messages to all slaves by specifying address 0. All slaves that receive a message from the
master execute the requested function. With this type of communication, slaves do not return a response to the master.
NOTE
During broadcast communication, functions are executed regarded of the set inverter station number (Pr.331).
Item Check time
Various monitors, operation command,
Frequency setting (RAM)
<12 ms
Parameter read/write,
frequency setting (EEPROM)
<30 ms
Parameter clear / all clear <5 s
Reset command No answer
Query communication
Broadcast communication
Query Message
Query Message
Response Message
Inverter (slave)
Inverter (slave)
Programmable controller
(Master)
Programmable controller
(Master)
No Response
Inverter response time
(Refer to the following table for the
data check time)
Data absence time
(3.5 bytes or more)