(D) Operation command and frequency command
320
PARAMETERS
Operation at fault
Selectable with Pr.75 Reset selection/disconnected PU detection/PU stop selection
Selectable with Pr.122 PU communication check time interval, Pr.336 RS-485 communication check time interval, and Pr.548 USB
communication check time interval
Follows the communication option
In the PU JOG operation mode, operation always stops when the PU is disconnected. The operation of PU disconnection (E.PUE) follows the
Pr.75 Reset selection/disconnected PU detection/PU stop selection setting.
When Pr.550 NET mode operation command source selection= "1" (RS-485 terminals enabled), or Pr.550 NET mode operation command
source selection="9999" with no communication option connected.
When Pr.550 NET mode operation command source selection="0" (communication option enabled), or Pr.550 NET mode operation
command source selection="9999" with communication option connected.
Fault record
Conditions
(Pr.551 setting)
Operation in each operation mode at error occurrences
PU
operation
External
operation
External/PU
combined
operation
mode 1
(Pr.79 =3)
External/PU
combined
operation
mode 2
(Pr.79 =4)
NET
operation
(when RS-485
terminals are
used)
NET operation
(when
communication
option is
used)
Inverter fault Stop
PU connector
disconnection
2 (PU connector)
9999 (automatic
recognition)
Stop/continued
Other than 2 Stop/continued
Communication
error at PU
connector
2 (PU connector)
Stop/
continued
Continued
Stop/
continued
Continued
Other than 2 Continued
Communication
error at RS-485
terminals
1 (RS-485
terminals)
Stop/
continued
Continued
Stop/
continued
Continued
Other than 1 Continued
Stop/continued
Continued
Communication
error at USB
connector
3 (USB
connector)
9999 (automatic
recognition)
Stop/
continued
Continued
Other than 3 Continued
Communication
error at
communication
option
Continued
Stop/continued