(A) Application parameters
552
PARAMETERS
Trigger setting (Pr.1025, Pr.1035 to Pr.1037, Pr.1046, Pr.1047)
Set the trigger generating conditions and trigger target channels.
Set the trigger generation conditions for the analog monitor.
 For Pr.1037, set the number obtained by adding 1,000 to the trigger level.
Set the trigger generation conditions for the digital monitor.
Pr.1025
setting
Trigger generating conditions
Selection of trigger
target channel
0 Trace starts when inverter enters an fault status (protective function activated)
1 Trace starts when analog monitor satisfies trigger conditions Pr.1035
2 Trace starts when digital monitor satisfies trigger conditions Pr.1046
3 Trace starts when either of analog or digital monitor satisfies trigger conditions (OR) Pr.1035, Pr.1046
4 Trace starts when both of analog or digital monitor satisfies trigger conditions (AND) Pr.1035, Pr.1046
Pr.1036
setting
Trigger generation conditions Trigger level setting
0
Sampling starts when the analog data targeted for the trigger exceeds the value
specified at the trigger level
Set the trigger level by
Pr.1037 (-400% to 400%)

1
Sampling starts when the analog data targeted for the trigger has fallen below the value
specified at the trigger level
Pr.1047
setting
Trigger generation conditions
0 Trace starts when the digital data targeted for the trigger turns ON
1 Trace starts when the digital data targeted for the trigger turns OFF