(A) Application parameters
552
PARAMETERS
Trigger setting (Pr.1025, Pr.1035 to Pr.1037, Pr.1046, Pr.1047)
• Set the trigger generating conditions and trigger target channels.
• Set the trigger generation conditions for the analog monitor.
For Pr.1037, set the number obtained by adding 1,000 to the trigger level.
• Set the trigger generation conditions for the digital monitor.
Pr.1025
setting
Trigger generating conditions
Selection of trigger
target channel
0 Trace starts when inverter enters an fault status (protective function activated) —
1 Trace starts when analog monitor satisfies trigger conditions Pr.1035
2 Trace starts when digital monitor satisfies trigger conditions Pr.1046
3 Trace starts when either of analog or digital monitor satisfies trigger conditions (OR) Pr.1035, Pr.1046
4 Trace starts when both of analog or digital monitor satisfies trigger conditions (AND) Pr.1035, Pr.1046
Pr.1036
setting
Trigger generation conditions Trigger level setting
0
Sampling starts when the analog data targeted for the trigger exceeds the value
specified at the trigger level
Set the trigger level by
Pr.1037 (-400% to 400%)
1
Sampling starts when the analog data targeted for the trigger has fallen below the value
specified at the trigger level
Pr.1047
setting
Trigger generation conditions
0 Trace starts when the digital data targeted for the trigger turns ON
1 Trace starts when the digital data targeted for the trigger turns OFF