EasyManua.ls Logo

Mitsubishi FR-A800

Mitsubishi FR-A800
746 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
(T) Multi-Function Input Terminal Parameters
412
PARAMETERS
NOTE
After changing the Pr.73 setting, check the voltage/current input switch setting. Incorrect setting may cause a fault, failure or
malfunction. (For the settings, refer to page 406.)
Override function (Pr.252, Pr.253)
NOTE
To use terminal 4, the AU signal needs to be turned ON.
To make compensation input for the multi-speed operation or remote setting, set Pr.28 Multi-speed input compensation
selection = "1" (with compensation) (initial value "0").
After changing the Pr.73 setting, check the voltage/current input switch setting. Incorrect setting may cause a fault, failure or
malfunction. (For the settings, refer to page 406.)
???????
Parameters referred to
Pr.28 Multi-speed input compensation selection page 328
Pr.73 Analog input selection page 406
Connection example for the
override function
Use the override function to make the main speed changed at a specified rate.
•Set Pr.73 = "4, 5, 14, or 15" to select the override function.
When the override function is selected, terminal 1 or 4 is used for the main speed
setting, and terminal 2 is used for the override signal. (if the main speed is not input
to the terminal 1 or 4, the compensation by terminal 2 is disabled.)
Specify the scope of override by using Pr.252 and Pr.253.
How to calculate the set frequency for override:
Set frequency (Hz) = main speed setting frequency (Hz)
Main speed setting frequency (Hz): Terminals 1 or 4 input, multi-speed setting
Compensation (%): Terminal 2 input
Example) When Pr.73 = "5"
By the terminal 1 (main speed) and terminal 2 (auxiliary) input, the
setting frequency is set as shown in the figure below.
10
2
5
Forward
rotation
Main
speed
Inverter
STF
SD
1
(-)
(+)
Override
setting
compensation (%)
100 (%)
Pr.252
0V
2.5V
(5V)
5V
(10V)
0
50
100
150
200
Initial value
(50% to 150%)
Voltage across terminals 2 and 5
Pr.253
Override value (%)
0 2.5 5
0
30
15
60
45
90
Terminal 1 input voltage (V)
Terminal 2 5VDC
input(150%)
Terminal 2 2.5VDC
input(100%)
Terminal 2 0V
input(50%)
Set frequency (Hz)

Table of Contents

Related product manuals